Retrofit for the FutureThis week we popped in to one of the homes that we retrofitted in 2010/11 as part of a Government-funded project, Retrofit for the Future, to find out how it was performing.

The headline finding is that the house is now using 9% of the energy it previously used for space and water heating; down from 12493kWh to 1133kWh. Overall energy use has been reduced by 75%, with the carbon emissions from the remaining use offset by a cost-effective investment in off-site renewables.

We visited after one year and found that actual energy use was 47% less than that predicted by SAP. There has been a further significant fall since then. Over the intervening years, the average energy use has been 30% of the use originally predicted for space and water heating, ventilation and lighting; and total average use has been 50% of use in that first year.

We expect heat usage to remain steady at this lower level (for the current occupancy patterns) as the fall can be attributed to one-off factors in that first year:

  • the building was drying out
  • the thermal mass had no heat stored as the build completed in early autumn
  • the winter of 2010/11 was particularly cold

Use of energy for appliances and cooking remains the largest influence on energy use, forming two-thirds of annual use on average. As highlighted in previous posts this is very dependent on working patterns and the number of residents. The final 3% of energy use is by the metering system itself – with metering on 8 rings in the house to enable this analysis.

Last, but certainly not least, was the residents’ feedback. The most notable problem was a rain sensor on the automated Velux windows in the sunspace, but that has been repaired quickly enough, and the occupants continue to enjoy the comfort of their old but cheaper-to-heat home.